Quick Answer
Current = hp × 745.7 ÷ (√3 × volts × efficiency × power factor) for three-phase. A 10 hp, 460 V motor at 90% efficiency and PF 0.85 draws about 12.2 A per line. A 2 hp single-phase motor at 230 V (80%, PF 0.8) draws about 10.1 A.
Embed this calculator
Adjust the size if needed, then copy the code below into your page or blog. The calculator will load in an iframe and stay updated automatically.
Table of Contents
- HP to Amps Calculator
- Quick Answer
- Related Calculators
- How This HP to Amps Calculator Works
- How to Use the HP to Amps Calculator
- Core Formulas
- Key Terms
- Worked Example
- Real-Life Examples
- Nameplate FLA vs Calculated Amps
- Estimated Amps for Three-Phase Motors
- Checking a Motor in the Field
- Notes on Motor Current
- Common Mistakes to Avoid
- Frequently Asked Questions
- References & Sources
How This HP to Amps Calculator Works
A motor’s horsepower rating is the mechanical power at its shaft. To deliver it, the motor draws more electrical power, because of losses (efficiency) and, on AC, because of reactive current (power factor). The calculator converts horsepower to watts (1 hp = 745.7 W), divides by efficiency for the input power, then by the voltage, power factor and, for three-phase, √3 to estimate the current.
Maintenance staff and electricians check many motors; save each one with its nameplate values.
Quick explanation:
- Watts out: hp × 745.7.
- Watts in: watts out ÷ efficiency.
- Amps: watts in ÷ (V × PF), × 1/√3 for three-phase.
How to Use the HP to Amps Calculator
- Choose DC, single-phase or three-phase.
- Enter the motor horsepower and the supply voltage.
- Enter the efficiency and power factor from the nameplate.
- Press Calculate for the estimated current and input power.
- Save the motor with its nameplate values.
Core Formulas
- Output power: Pout = hp × 745.7 W
- Input power: Pin = Pout ÷ efficiency
- DC: I = Pin ÷ V
- Single-phase: I = Pin ÷ (V × PF)
- Three-phase: I = Pin ÷ (√3 × V × PF)
Key Terms
- Horsepower: a unit of power; 1 hp ≈ 745.7 W.
- Efficiency: output power ÷ input power.
- Power factor: real power ÷ apparent power.
- FLA: full-load amps, on the motor nameplate.
- Line-to-line voltage: voltage between two phases.
Worked Example
A 50 hp three-phase motor at 460 V, 93% efficiency, PF 0.88.
- Output = 50 × 745.7 = 37,285 W
- Input = 37,285 ÷ 0.93 = 40,091 W
- Current = 40,091 ÷ (1.732 × 460 × 0.88) = 57.2 A per line
Real-Life Examples
- 10 hp, 460 V three-phase pump: about 12.2 A.
- 2 hp, 230 V single-phase compressor: about 10.1 A.
- 50 hp, 460 V three-phase fan: about 57.2 A.
- 1 hp, 24 V DC motor at 85%: about 36.6 A.
Nameplate FLA vs Calculated Amps
- Nameplate FLA: measured for that motor at rated load; use it when you have it.
- Calculated amps: a good estimate when you only know hp, efficiency and power factor.
- Code tables: standardized values used for sizing in many codes.
Estimated Amps for Three-Phase Motors
| hp | 208 V | 230 V | 460 V |
|---|---|---|---|
| 1 | 2.7 A | 2.4 A | 1.2 A |
| 2 | 5.4 A | 4.9 A | 2.4 A |
| 3 | 8.1 A | 7.3 A | 3.7 A |
| 5 | 13.5 A | 12.2 A | 6.1 A |
| 7.5 | 20.3 A | 18.4 A | 9.2 A |
| 10 | 27.1 A | 24.5 A | 12.2 A |
| 15 | 40.6 A | 36.7 A | 18.4 A |
| 20 | 54.1 A | 48.9 A | 24.5 A |
| 25 | 67.6 A | 61.2 A | 30.6 A |
| 50 | 135.3 A | 122.3 A | 61.2 A |
Checking a Motor in the Field
Compare the estimate with the nameplate full-load amps and with a clamp-meter reading on each line. A running current well above the estimate can point to overload, low voltage, a mechanical problem or an unbalanced supply; a current far below it usually means the motor is lightly loaded. Save each motor with its nameplate values and the readings you took, and you have a simple log to compare with next time. Remember that starting current is much higher and is not shown here.
Notes on Motor Current
- Nameplate first: the nameplate full-load amps (FLA) is the best figure for a specific motor.
- Starting current: motors draw several times more current while starting; this calculator gives running current.
- Partial load: efficiency and power factor change at light load.
- Code tables: conductor and protection sizing may be based on code tables, not on this estimate.
- Voltage: use the actual supply voltage; for three-phase, line-to-line.
Common Mistakes to Avoid
- Using 746 W as input power. Horsepower is output; divide by efficiency.
- Forgetting √3 on three-phase.
- Ignoring power factor on AC. It raises the current.
- Sizing on running current only. Consider starting current and code rules.
- Using phase voltage for three-phase. Use line-to-line.
Frequently Asked Questions
Amps = hp × 745.7 ÷ (volts × efficiency × power factor), and ÷ √3 more for three-phase.
At 460 V three-phase, 90% and PF 0.85, about 12 A.
About 745.7 W.
Efficiency losses and power factor both raise the current.
No; use the nameplate FLA when you have it.
No, it is running current.
Yes; choose DC.
Yes. Save each one by name.
Yes. Use Compare: keep as A.
The nameplate value.
The nameplate value at full load.
Use code tables for sizing; this is an estimate.
Yes. Press Print.
Divide kW by 0.7457 to get hp, or use the Watts to Amps Calculator.
References & Sources
| Source | Used For | Link |
|---|---|---|
| Wikipedia, Horsepower | 1 hp ≈ 745.7 W; motor nameplates state shaft output power. | https://en.wikipedia.org/wiki/Horsepower |
| Wikipedia, Power factor | Real power ÷ apparent power. | https://en.wikipedia.org/wiki/Power_factor |
| Wikipedia, Three-phase electric power | Line voltage = √3 × phase voltage. | https://en.wikipedia.org/wiki/Three-phase_electric_power |