Quick Answer
Power factor = kW ÷ kVA. A load using 80 kW from a 100 kVA supply has a power factor of 0.80 and 60 kVAR of reactive power. Raising it to 0.95 takes about 33.7 kVAR of capacitors and cuts the apparent power to 84.2 kVA.
Embed this calculator
Adjust the size if needed, then copy the code below into your page or blog. The calculator will load in an iframe and stay updated automatically.
Table of Contents
- Power Factor Calculator
- Quick Answer
- Related Calculators
- How This Power Factor Calculator Works
- How to Use the Power Factor Calculator
- Core Formulas
- Key Terms
- Worked Example
- Real-Life Examples
- Real, Reactive and Apparent Power
- Correction Capacitor per kW
- Reading Your Results
- Why Power Factor Matters
- Common Mistakes to Avoid
- Frequently Asked Questions
- References & Sources
How This Power Factor Calculator Works
Power factor compares the power that does useful work (real power, kW) with the power the wiring and equipment must carry (apparent power, kVA). Enter kW and kVA from a meter or nameplate, or enter watts, volts and amps and the calculator works out the apparent power for single- or three-phase. You get the power factor, the reactive power (kVAR), the phase angle and, if you set a target, the capacitor kVAR needed for power factor correction.
Facility and maintenance staff check loads regularly; save each load and compare before and after correction.
Quick explanation:
- PF: kW ÷ kVA, from 0 to 1.
- kVAR: √(kVA² − kW²).
- Correction: capacitors supply kVAR so the supply carries less.
How to Use the Power Factor Calculator
- Choose whether you know kW and kVA, or watts, volts and amps.
- Enter the values (and the system type for volts and amps).
- Enter a target power factor if you plan correction.
- Press Calculate to see PF, kVAR and the capacitor size.
- Save the load and compare after changes.
Core Formulas
- Power factor: PF = P ÷ S (kW ÷ kVA)
- Apparent power from V and A: S = V × A (single-phase), √3 × V × A (three-phase), ÷ 1,000 for kVA
- Reactive power: Q = √(S² − P²)
- Phase angle: φ = arccos(PF)
- Correction capacitors: Qc = P × (tan φnow − tan φtarget)
Key Terms
- Power factor: real power divided by apparent power.
- kVAR: reactive power.
- Phase angle: the angle between voltage and current.
- Lagging PF: current lags voltage, typical of motors.
- Capacitor bank: capacitors added to supply reactive power.
Worked Example
A motor load draws 45 kW and 60 kVA. The utility wants 0.95.
- PF = 45 ÷ 60 = 0.75; angle = 41.4°
- kVAR now = √(60² − 45²) = 39.7
- kVAR at 0.95 = 45 × tan(arccos 0.95) = 14.8
- Capacitors needed ≈ 24.9 kVAR; apparent power drops to 47.4 kVA
Real-Life Examples
- Plant load 80 kW / 100 kVA: PF 0.80; about 33.7 kVAR to reach 0.95.
- Motor 45 kW / 60 kVA: PF 0.75; about 24.9 kVAR to reach 0.95.
- Heat pump 18 kW / 19.5 kVA: PF 0.923; correction to 0.98: 3.8 kVAR.
- Single-phase check: 4,500 W at 240 V and 22 A gives PF 0.85.
Real, Reactive and Apparent Power
- Real power (kW): does the work: heat, light, motion.
- Reactive power (kVAR): flows back and forth to build magnetic and electric fields.
- Apparent power (kVA): the combination the supply must carry: √(kW² + kVAR²).
Correction Capacitor per kW
| PF now | to 0.90 | to 0.95 | to 1.00 |
|---|---|---|---|
| 0.60 | 0.849 | 1.005 | 1.333 |
| 0.65 | 0.685 | 0.840 | 1.169 |
| 0.70 | 0.536 | 0.692 | 1.020 |
| 0.75 | 0.398 | 0.553 | 0.882 |
| 0.80 | 0.266 | 0.421 | 0.750 |
| 0.85 | 0.135 | 0.291 | 0.620 |
| 0.90 | – | 0.156 | 0.484 |
Reading Your Results
The table shows the same load in several ways. The power factor itself is the share of the supplied power that does work. The reactive power is the part that only flows back and forth; it does not show up as useful output, but it still loads the cables, transformer and switchgear. The phase angle tells you how far the current lags the voltage. If you entered a target, the capacitor line is the size of the correction you would discuss with an electrician or supplier, and the last line shows how much the apparent power, and so the current, would fall.
Why Power Factor Matters
- Bigger currents: a low power factor means more current for the same work, so larger wires and equipment.
- Utility charges: Wikipedia notes utilities often charge industrial or commercial customers more for a low power factor.
- Losses: higher current raises the energy lost in distribution.
- Causes: induction motors and other inductive loads lower power factor.
- Harmonics: non-linear loads distort current; capacitor correction alone may not fix that.
Common Mistakes to Avoid
- Real power larger than apparent. That means a measurement error.
- Forgetting √3 on three-phase. Use line-to-line volts with √3.
- Over-correcting. Too many capacitors can make the power factor leading.
- Ignoring harmonics. Non-linear loads need more than capacitors.
- Using nameplate PF at light load. PF changes with load.
Frequently Asked Questions
Divide real power (kW) by apparent power (kVA).
Closer to 1 is better; many utilities set a minimum in their tariffs.
√(kVA² − kW²).
kVAR = kW × (tan(arccos PF now) − tan(arccos PF target)).
No. If you get more than 1, check your readings.
Mostly inductive loads such as motors and transformers.
Yes. Choose single-phase when entering volts and amps.
Yes. Save each load by name.
Yes. Use Compare: keep as A.
It can cause problems too; avoid over-correction.
About 36.9 degrees.
Yes. Press Print.
Yes; lightly loaded motors usually have a lower PF.
No; it is a quick estimate.