Convert amps to kVA or kVA to amps for single-phase or three-phase circuits, and see kW and kVAR at your power factor. For sizing transformers, generators and services. Save each job.

Results

ItemValue
Single-phase: kVA = V × A ÷ 1,000. Three-phase (balanced): kVA = √3 × V(line-to-line) × A ÷ 1,000, because the apparent power is 3 × V(phase) × A and V(line) = √3 × V(phase). Real power kW = kVA × power factor; reactive power kVAR = kVA × √(1 − PF²). For conductor, breaker and transformer sizing follow the electrical code and the equipment nameplate.

Quick Answer

Three-phase: kVA = 1.732 × volts × amps ÷ 1,000. A 480 V three-phase load drawing 50 A is 41.57 kVA, or 35.33 kW at a power factor of 0.85. Single-phase: kVA = volts × amps ÷ 1,000, so 240 V at 100 A is 24 kVA.

Last updated: 27 November 2026 ·How we calculate this: kVA = √3 × V × A ÷ 1,000 (three-phase)

How This kVA Calculator Works

Transformers, generators and UPS units are rated in kVA, the apparent power they can deliver, while loads are often listed in amps. Choose whether you know the amps or the kVA, pick single- or three-phase, and enter the voltage (line-to-line for three-phase). The calculator converts one to the other and, with a power factor, shows the real power in kW and the reactive power in kVAR.

Electricians and engineers size equipment all the time; save each job and compare options side by side.

Quick explanation:

  • Single-phase: kVA = V × A ÷ 1,000.
  • Three-phase: kVA = 1.732 × V × A ÷ 1,000.
  • kW: kVA × power factor.

How to Use the kVA Calculator

  1. Choose whether you know amps or kVA.
  2. Choose single-phase or three-phase.
  3. Enter the voltage (line-to-line for three-phase).
  4. Enter the amps or kVA and, if known, the power factor.
  5. Read kVA, amps, kW and kVAR; Save the job.

Core Formulas

  • Single-phase apparent power: S (kVA) = V × I ÷ 1,000
  • Three-phase apparent power: S = 3 × Vphase × I ÷ 1,000 = √3 × Vline × I ÷ 1,000
  • Current from kVA: I = S × 1,000 ÷ V (single-phase) or ÷ (√3 × V) (three-phase)
  • Real power: P (kW) = S × power factor
  • Reactive power: Q (kVAR) = S × √(1 − PF²)

Key Terms

  • kVA: kilovolt-amperes: apparent power.
  • kW: kilowatts: real power.
  • kVAR: kilovolt-amperes reactive: reactive power.
  • Power factor: real power ÷ apparent power.
  • Line-to-line voltage: the voltage between two phase conductors.

Worked Example

A 75 kVA three-phase transformer at 208 V: what is its full-load current?

  • I = 75,000 ÷ (1.732 × 208) = 208.2 A per line
  • At PF 0.85 it can deliver 63.75 kW of real power
  • A 22 kVA single-phase generator at 240 V gives 91.7 A

Real-Life Examples

  • 480 V three-phase motor load at 50 A: 41.57 kVA.
  • 240 V single-phase service at 100 A: 24 kVA.
  • 75 kVA transformer at 208 V three-phase: 208.2 A full-load current.
  • 22 kVA standby generator at 240 V: 91.7 A.

kVA vs kW

  • kVA (apparent power): volts × amps; what the wiring, transformer or generator must carry.
  • kW (real power): the power that does work; kVA × power factor.
  • At PF 1 they are equal; at lower PF the kVA is larger than the kW.

Full-Load Amps for Common Transformer Sizes

kVA208 V240 V480 V
1541.6 A36.1 A18.0 A
3083.3 A72.2 A36.1 A
45124.9 A108.3 A54.1 A
75208.2 A180.4 A90.2 A
112.5312.3 A270.6 A135.3 A
150416.4 A360.8 A180.4 A
225624.5 A541.3 A270.6 A
300832.7 A721.7 A360.8 A
5001387.9 A1202.8 A601.4 A

Sizing Notes

  • Use the right voltage: line-to-line for three-phase (208, 480 V); line-to-neutral loads are single-phase.
  • Power factor: motors and some electronics draw more kVA than kW; use the nameplate PF when you have it.
  • Balanced loads: the three-phase formula assumes the three lines carry equal current.
  • Margin and code: transformer and generator sizing also considers starting loads, growth and code requirements.
  • Units: 1 kVA = 1,000 VA; 1 kW = 1,000 W.
  • Read the nameplate: equipment labels list voltage, phase, full-load amps or kVA; start from those numbers rather than estimates whenever you can, and keep the saved job with the equipment record.

Common Mistakes to Avoid

  • Using line-to-neutral voltage in the three-phase formula. Use line-to-line.
  • Confusing kVA and kW. Multiply by power factor for kW.
  • Forgetting √3. Three-phase current is not kVA ÷ V.
  • Unbalanced loads. The formula assumes a balanced load.
  • Sizing at 100%. Leave margin as the code and the equipment maker require.

Frequently Asked Questions

Single-phase: V × A ÷ 1,000. Three-phase: 1.732 × V × A ÷ 1,000.

At 208 V three-phase about 208 A; at 480 V about 90 A.

kVA is apparent power; kW is real power, kVA × power factor.

Because the line-to-line voltage is √3 times the phase voltage.

The nameplate value if you have it; otherwise a realistic estimate for the load.

At 240 V single-phase about 92 A.

No. It converts units; follow the electrical code for sizing.

Yes. Save each one by name.

Yes. Use Compare: keep as A.

Use single-phase; for DC kVA equals kW.

Sizing power factor correction capacitors.

Yes. Press Print.

Because the generator must carry the current regardless of power factor.

1,000 VA.

References & Sources

SourceUsed ForLink
Wikipedia, Power factor Power factor = real power ÷ apparent power. https://en.wikipedia.org/wiki/Power_factor
Wikipedia, Three-phase electric power Line-to-line voltage = √3 × phase voltage; balanced loads. https://en.wikipedia.org/wiki/Three-phase_electric_power

Cite or share this calculator

DigitalCalculators.net. (2026, November 27). kVA Calculator. https://digitalcalculators.net/kva-calculator/